Common Causes of PLC Failure and How to Reduce the Risk

10 hours ago
8 min read
PLC Control System

When an automated production line suddenly stops, the PLC is often one of the first

things to be blamed.

Sometimes the PLC really has failed. But in many cases, what appears to be a PLC failure is actually a problem elsewhere in the control system.


A failed power supply, damaged sensor, faulty I/O module, communication problem or wiring fault can all prevent machinery from operating correctly while the PLC itself continues doing exactly what it has been programmed to do.


Understanding the common causes of PLC and control system failure can help engineering teams diagnose problems more quickly and, importantly, identify risks before they result in unexpected production downtime.


Does the PLC actually fail very often?


PLCs are designed specifically for industrial environments and are generally extremely reliable.

Unlike ordinary computers, they are built for continuous operation and are designed to tolerate the conditions typically encountered within industrial control systems.

However, reliable does not mean indestructible.


PLCs can remain in service for many years, sometimes considerably longer than originally anticipated. During that time they are affected by the condition of their power supplies, control panels, electrical environment, connected equipment and surrounding operating conditions.


Eventually, components can fail.

The challenge is determining whether the PLC itself is responsible or whether it is simply responding to another problem.


1. Power supply problems


One of the first areas to investigate when a PLC appears to have failed is its power supply.

A PLC requires a stable supply voltage to operate correctly. Problems with the incoming supply, a failing power supply unit, loose connections or damaged wiring can cause the controller to shut down or behave unexpectedly.


Intermittent power problems can be particularly frustrating because the machinery may operate normally for long periods before suddenly stopping.

Power quality problems can also affect other devices within the control system, including HMIs, remote I/O and communication equipment.


Before replacing a PLC processor, it therefore makes sense to confirm that the controller is actually receiving the correct and stable power supply.


2. Excessive heat


Heat is a major consideration in industrial control panel design.

PLCs, power supplies, variable speed drives and other electrical equipment all generate heat. If the panel cannot dissipate that heat effectively, internal temperatures can rise beyond suitable operating conditions.


Blocked ventilation, failed cooling equipment, dirty filters, overcrowded panels and additional components installed after the original design can all contribute to the problem.

The surrounding environment matters too.

A control panel positioned in an already hot production area faces different thermal conditions from one installed in a controlled electrical room.


Excessive temperature can shorten the life of electronic equipment and contribute to intermittent faults that become increasingly difficult to diagnose.

Good thermal design and routine panel maintenance therefore play an important role in protecting PLC hardware.


3. Dust, moisture and contamination


Industrial environments can expose electrical equipment to dust, moisture, oil, chemicals and other contaminants.

The control panel enclosure should provide appropriate protection for the environment in which it is installed.


Problems can develop when seals deteriorate, doors are repeatedly left open, cable entries are poorly sealed or modifications compromise the original enclosure protection.

Conductive contamination is particularly concerning because it can affect electronic equipment and electrical connections.


Moisture and condensation can also lead to corrosion and electrical problems.

A PLC may be a robust industrial controller, but it still relies on being installed in an environment appropriate for electronic equipment.


4. Failed I/O modules


A PLC system consists of more than the processor.

Input and output modules connect the controller to the machinery and process.

An input module might receive information from sensors and switches, while an output module controls devices such as relays, valves and contactors.

If an I/O channel or module fails, the resulting symptoms can easily be interpreted as a PLC problem.


For example, the PLC program may be waiting for confirmation from a sensor before allowing a machine sequence to continue. If the input module never receives that signal, the machine stops even though the processor itself is operating correctly.


Proper diagnostics involve tracing the signal from the field device through the wiring and I/O system rather than assuming the PLC program is responsible.


5. Sensor and field-device failures


A failed field device is another common reason for PLC-controlled machinery to stop.

Proximity sensors, photoelectric sensors, pressure switches, level instruments, encoders and other devices provide the PLC with information about the physical process.


If one fails, the PLC may receive information indicating that the required conditions for operation have not been met.

In many cases, stopping the machine is exactly what the PLC is supposed to do.


This is why an engineer looking at the PLC program may find that the controller is healthy but is waiting for a signal that never arrives.

Effective fault finding means identifying why the PLC is not receiving the expected condition.


6. Wiring and connection problems


Industrial machinery contains large numbers of electrical connections, and these can deteriorate over time.

Loose terminals, damaged cables, broken conductors, poor connections and modifications to existing wiring can all cause control problems.


Intermittent connections are particularly troublesome.

A machine might operate correctly when stationary but develop faults when vibration increases. A conductor may make contact most of the time and fail only under particular operating conditions.


Clear wire identification, accurate electrical drawings and good panel construction make these problems considerably easier to trace.

Without them, technicians may spend hours trying to determine whether a fault originates in the PLC, field equipment or wiring between the two.


7. Industrial network and communication faults


Modern PLCs communicate with increasing numbers of devices over industrial networks.

Remote I/O, variable speed drives, HMIs, SCADA systems, robots and other controllers may communicate through technologies such as PROFINET, EtherNet/IP or Modbus TCP.


If that communication is interrupted, parts of the machine may stop operating even though the PLC processor remains healthy.

Communication failures can result from damaged cables, connectors, network hardware, configuration errors, duplicate addressing, device faults or modifications to the system.


The symptoms can also be misleading.

A drive that appears to have stopped responding may simply have lost communication with the PLC.

Understanding the network architecture is therefore becoming an increasingly important part of PLC fault finding.


8. Electrical noise and interference


Industrial environments contain equipment capable of generating significant electrical noise.

Motors, variable speed drives, contactors and other switching equipment can all contribute to electromagnetic interference.


Appropriate panel design, cable routing, separation, screening, grounding and installation practices are important in reducing the effect of interference on control equipment.


Problems in this area can sometimes produce intermittent or apparently random symptoms rather than a straightforward permanent failure.

These are often some of the more difficult automation problems to diagnose because the fault may disappear before an engineer has an opportunity to investigate it.


9. Battery or memory-related issues on older PLCs


Older PLC platforms may rely on batteries to retain certain memory or data.

If these batteries are not replaced according to the appropriate maintenance requirements, important information can potentially be lost when the controller is powered down.


The exact behaviour varies considerably between PLC manufacturers and generations, so it is important to understand the particular hardware installed.

This becomes especially relevant on ageing machinery where the PLC may have operated continuously for years and nobody is certain when its battery was last inspected or replaced.


Older systems should therefore be reviewed according to their specific maintenance requirements rather than assuming modern PLC practices apply to them.


10. Software and program problems


Not every PLC-related failure is a hardware failure.

Software modifications can introduce unexpected behaviour.

A change intended to solve one production issue may affect another part of the machine sequence. Incorrect parameters, poorly considered interlocks or modifications made without appropriate testing can all create problems.


Another risk arises when the PLC program running in the machine no longer matches the backup held by the engineering team.

If the controller then needs replacing, restoring an outdated program could reintroduce faults or remove modifications that have been made since the backup was created.


PLC software should therefore be treated as a controlled engineering asset, with appropriate backups and revision management.


11. Obsolete PLC hardware


Some of the most serious PLC risks are not caused by an immediate failure but by obsolescence.

A PLC may continue operating reliably long after the manufacturer has discontinued the platform.


That can create a false sense of security.

The problem only becomes obvious when a processor, I/O module or communication component eventually fails and an equivalent replacement is difficult to obtain.

Businesses can then find themselves searching for refurbished or second-hand components while production is already stopped.


This is why PLC obsolescence should ideally be addressed while the equipment is still operational.

A planned PLC upgrade or migration provides considerably more control over testing, commissioning and production disruption than an emergency replacement following a failure.


12. Changes made over many years


Industrial control systems evolve.

Machines are modified. Sensors are replaced. Additional equipment is installed.

Production requirements change and temporary fixes are introduced to keep equipment running.


Individually, each change may make sense.

Collectively, however, years of undocumented modifications can create a control system that bears little resemblance to its original drawings and software documentation.


When a fault occurs, engineers are then trying to diagnose a system they cannot completely see.

This is why maintaining accurate electrical drawings, PLC backups and change records is so important.

Documentation does not prevent components from failing, but it can significantly reduce the time required to understand what has failed.


What are the warning signs of a developing PLC problem?


Not every control system failure happens without warning.

Engineering teams may begin to notice intermittent communication faults, unexplained PLC resets, increasing I/O problems, unusual temperature inside the control panel or components that require repeated replacement.


Operators may also report occasional machine faults that disappear after a reset.

Repeated resets deserve particular attention.

Resetting equipment may restore production, but it does not explain why the fault occurred.


If the same problem repeatedly returns, investigating the root cause can prevent a relatively minor issue from eventually causing a more significant production stoppage.


What should you check when a PLC-controlled machine stops?


The first step should be understanding what the control system is telling you.

  • Is the PLC powered?

  • Is the processor running normally?

  • Are any hardware diagnostic indicators showing a fault?

  • Are the expected inputs present?

  • Are remote I/O or network devices communicating?

  • Has a drive or another connected device reported a fault?

  • Is the PLC program waiting for a particular condition?


The objective is to narrow the problem down systematically.

Replacing components without confirming the cause can waste time and sometimes introduce additional faults.


A PLC should not be replaced simply because the machine it controls has stopped.


Preventing PLC failure is about the whole control system


Reducing the risk of PLC-related downtime requires looking beyond the PLC itself.

Control panels should be kept clean and maintained appropriately. Cooling and ventilation equipment should be checked. Electrical connections should be inspected according to the site's maintenance strategy, and recurring faults should be investigated rather than continually reset.


Engineering teams should also know which PLC platforms are installed, whether they remain supported and what critical spares are available.

Most importantly, current PLC programs and electrical documentation should be accessible before an emergency occurs.


Preventative maintenance cannot eliminate every failure.

It can, however, turn many unexpected breakdowns into known risks that can be planned and managed.


Don't wait for an obsolete PLC to fail


A PLC that has run reliably for twenty years may continue operating tomorrow.

It may also fail tomorrow.

Where critical machinery depends on ageing or obsolete automation equipment, understanding that risk allows the business to make a planned decision rather than an emergency one.


Sometimes the right solution is improved maintenance or better spares provision.

In other cases, a PLC migration or wider control system upgrade may provide the more sustainable approach.

At Stratos Control Systems, we support businesses with PLC fault finding, programming, upgrades and migration across Siemens, Allen-Bradley and Mitsubishi control systems.


Whether a machine has stopped unexpectedly, an intermittent fault keeps returning or an ageing PLC platform is becoming increasingly difficult to support, identifying the actual cause is the first step towards a reliable solution.


Speak to Stratos Control Systems about PLC fault finding, programming, upgrades and industrial automation support.