What Makes a Good Control Panel Design?

Good control panel design is judged on the day somebody who did not build it has to find a fault, fast. Layout, separation, identification, the standards behind it, and what changes when the environment is a washdown area.

9 March 2026

Two Stratos engineers in branded polo shirts reviewing electrical schematics and a component catalogue at a desk

Good control panel design is judged on a day nobody plans for: the day somebody who did not build it has to find a fault in it, quickly, with the line down.

What industrial control panel design covers

It runs from the electrical schematic through component selection, panel layout, wiring and terminal design, to integration with the PLC and SCADA and HMI systems the panel serves. Drawn in EPLAN Electric P8 or AutoCAD Electrical, the design is also the document the panel is built from, tested against and maintained with for the rest of its life.

Good against poor control panel design

Good designPoor design
LayoutRelated components grouped, consistent conventions, space to workFilled to capacity, arranged around whatever fitted
SeparationPower and control segregated, voltage levels zonedMains and extra-low-voltage in the same trunk
IdentificationWire numbers, terminal numbers and component tags matching the drawingsPartial labelling, inconsistent naming, nothing tying panel to schematic
Cable managementRouted, contained, room for the next changeLoose bundles, insulation chafing where nobody looks
DocumentationSchematics, I/O lists, terminal plans and component schedules issued as-builtA drawing set that describes the panel as it was first delivered
ExpansionSpare terminals, spare I/O, physical space left deliberatelyNo room, so the next addition goes wherever it fits

The standards behind control panel design

BS EN 61439 governs the assembly: temperature rise, short-circuit withstand, dielectric properties and degree of protection. BS EN 60204-1 covers the electrical equipment of machinery, including emergency stop, isolation and protective bonding. Between them they set most of what a design has to answer for.

Designing for the environment

Ingress protection is a design decision, not a catalogue choice. IP54 suits an indoor plant room. A washdown area in food or beverage production needs IP65 or IP66 and a stainless enclosure, with sloped tops and no crevices that trap water. Thermal calculations belong here too, because drives, transformers and power supplies all put heat into the enclosure and the ambient temperature of a plant room in August is not the one on the datasheet.

New panel design or improving an existing one

New build allows a layout drawn for the system rather than inherited from it, and drawings that match the panel from day one. Refurbishment keeps a sound enclosure and spends the money on what is inside: obsolete components replaced, layout improved, wiring re-run and identified. Where drawings have been lost, re-documenting the panel is usually the first job worth doing, because every subsequent intervention depends on it.

What it is worth

Layout and labelling decide how long fault finding takes, every time, for fifteen years. That is the return on control panel design, and it is why we treat the drawing set as the deliverable rather than the paperwork. Our control panel design and build work is organised on that basis.

Frequently asked questions

What makes a good control panel design?

A layout somebody who did not build it can read: related components grouped, power and control segregated, identification carried through to the drawings, space left for the additions that always come, and a documentation pack that matches what was actually built.

What standards apply to control panel design in the UK?

BS EN 61439 for the assembly and BS EN 60204-1 for the electrical equipment of machinery. Which apply depends on the application and whether the panel forms part of a machine.

Why is control panel layout important?

It sets how long every future intervention takes. An overcrowded panel means no room to probe, longer exposure to live parts, and heat with nowhere to go. A structured one means a fault can be traced by anyone competent, not only by whoever built it.

How does control panel design affect downtime?

Through mean time to repair rather than failure rate. Clear identification, accurate drawings and accessible components are what turn an hour's fault into twenty minutes.

Can control panels be improved after installation?

Yes. Refurbishment can replace obsolete components, improve layout, re-run and identify wiring, and re-document a system nobody has accurate drawings for, all while keeping a sound enclosure.

Ready to talk through your automation challenge?

Tell us what the system needs to do, or what it is doing that it should not. You will speak to an engineer, not an account manager.